0

Transformer Evacuation System

Transformer Evacuation System
Transformer Evacuation System
Price And Quantity
  • Unit/Units
  • 1
  • Piece/Pieces
  • 500000 INR
    Product Specifications
    • Transformer Evacuation, Other
    • Steel
    • No
    • Semi-Automatic
    • 220-480 Volt (v)
    Product Description

    Transformer Evacuation System

    Transformers are key equipments, and it is much imperative to maintain the optimal insulation properties of the transformer oils by rigid control over moisture, dissolved gases and particulate contamination. Vacuum is drawn in transformer tank with assistance of transformer evacuation system in order to take off gases and from insulation/oil. Alternately during the commissioning of transformers, nitrogen is evacuated with transformer evacuation system before new oil filling in transformers. It is a wet process which postulates proper moisture extraction before its debut into vacuum pump. The conditioning applied in this system saves the cost of frequent uses of new oil, and enhances the life of the transformers. This system has complete turnkey applications, and come with spare parts and technical support network. The oil and vacuum connections provided in this system is in the form of flanged joint with 'O' Ring, that ensures full sealing efficiency at all times and thus requires minimal maintenance.

    Features:

    • Avoid breakdown of voltage, ionic reaction column.

    • Insulation resistance, Gas & Moisture Measuring Instruments, Fail proof interlocking system.

    • Optional hot oil circulation / on-site drying, filters press.

    • Fuse-less control panel, 3 piece valves with PTFE seating and stainless steel balls.

    Optional

    • Transformer Evacuation System
    • Hot Oil Circulation / On-site Drying
    • Filters Press, Ionic Reaction Column
    • Flow meter
    • Gas & Moisture Measuring Instruments
    • Condensers
    • Audio / Visual annunciation

    Oil Conditioning Machines Technical Parameters

    Description Models

    JMHV

    JHV

    JHVR

    Vacuum Level at Final Oil Run Through (in torr)

    <3

    < 1

    < 0.5

    Unprocessed Oil Quality

    Water content (Max.) ppm

    50

    50

    50

    Gas content (Max.) % vol.

    10

    10

    10

    Break down voltage kV

    20

    20

    20

    Oil Quality After Single Pass

    Water content (Max.) ppm

    20

    6

    3

    Gas content (Max.) % vol.

    2

    0.5

    0.1

    Break down voltage kV

    50

    60

    65

    Oil Quality After Two Passes

    Water content (Max.) ppm

    10

    3

    2

    Gas content (Max.) % vol.

    1

    0.1

    0.05

    Break down voltage kV

    60

    70

    75

    Technical Parameters
    The parameters shown confirm and betters IS & IEC Standards.

    Standard capacities (LPH)
    200, 600, 1200, 2400, 3000, 4000, 4500, 5000, 6000, 10000, 12000 and above.

    Power Supply
    415V, 3 phase, 50 Hz

    * Under Test Conditions

    Trade Information
    • Cash in Advance (CID), Cash Advance (CA)
    • 1 Per Day
    • 4 Week
    • All India
      Contact Us

      Plot # 60 to 63, 4th Phase, KIADB Industrial Area, Malur, Karnataka, 563130, India
      Phone :91-8152-282500